What it calculates
The calculator estimates how much capacitive reactive power would offset the change between two supplied lagging power factors while real load power remains constant.
Use measured electrical input kW and power-factor values for the same load and operating condition. Enter each power factor as a percentage from greater than 0% through 100%; the target must be at least the current value.
Method and example
For real power P and power factor PF, the reactive-power magnitude is Q = P × √(1 − PF²) ÷ PF. Required correction is the initial reactive-power magnitude minus the target reactive-power magnitude. The tool converts entered percentages to ratios before calculating.
For 100 kW at 75% lagging power factor, targeting 95% gives about 88.192 kVAr initially, 32.868 kVAr at the target, and 55.323 kVAr of calculated correction.
Limits and interpretation
The calculation assumes a steady real-power load, sinusoidal quantities, and lagging power factor represented by the supplied values. A meter's true power factor on a distorted waveform may not fit this model.
The result is not a capacitor-bank rating or design. It does not model changing loads, resonance, harmonics, switching transients, system impedance, voltage rise, protection, utility billing, or equipment limits. Confirm the actual installation and utility requirements with the relevant qualified professional.
No universal target, savings, pass/fail threshold, utility acceptance or code conclusion is applied.
Common questions
Why must the target be no lower than the current factor?
This tool calculates capacitive correction only. A lower target would increase the reactive-power requirement rather than correct the supplied starting condition.
Does the result tell me which capacitor to install?
No. The arithmetic does not select a capacitor rating, bank arrangement, switching method, protection or installation location.
Can I use total kVA or motor shaft power as the real power?
Use electrical input power in kW for the same operating point. Motor shaft output and apparent power are different quantities.
Related tools
These calculators report other electrical quantities and do not select compensation equipment.
Sources
Eaton Canada, Power Factor Correction: A Guide for the Plant Engineer, document SA02607001E, effective August 2014, printed pp. 12–13, including Table 6's 75%-to-95% multiplier. Checked November 10, 2026. Its plant-engineering and equipment guidance is not implemented.
The guide's plant-engineering examples provide industrial context; they do not establish residential use, a universal correction target, a capacitor-bank design or equipment approval.