Conductors and circuit performance

Voltage drop calculator

Estimate physical voltage drop using supplied effective impedance or a listed Southwire RW90 copper row under its stated conditions. No conductor is recommended and no code decision is provided.

Calculation inputs

Circuit details

V

Use circuit voltage for a two-wire single-phase circuit; line-to-line voltage for a balanced three-phase circuit.

A

Use line current consistent with the effective-impedance method and load power factor. Do not apply the power factor twice.

m

Enter the one-way physical run length. The phase factor accounts for the return path in this simplified method.

Ω/km

Enter effective impedance suitable for the conductor and conditions. The limited Southwire RW90 AC mode is available as a separate source option.

Use voltage and current values from the same circuit operating point.

Example values are loaded from NRC Example 7-1: 208 V, 50 A, 30.5 m and 1.48 Ω/km supplied effective impedance. Replace them with the job's measured or documented values.

Enable JavaScript in your browser to use the calculator.

Voltage drop

Enter values to calculate. No acceptability or conductor recommendation is provided.

Method and limits

The manual mode uses effective impedance supplied by the user. For two-wire single-phase circuits, the relationship is ΔV = 2 × I × L × Z ÷ 1000. For balanced three-phase circuits, it is ΔV = √3 × I × L × Z ÷ 1000. Current is in amperes, one-way length is in metres, and impedance is in ohms per kilometre. Maximum distance algebraically rearranges the selected relationship using a target percentage supplied by the user.

The percentage-to-volts mode multiplies the supplied reference voltage by the percentage entered. It is a direct arithmetic conversion only; it does not assess a circuit or recommend a target. Converted values may exceed the reference voltage.

The limited DC mode uses listed Southwire RW90 copper DC resistance at 25°C for 14, 12 or 10 AWG solid or seven-strand products, and 8 AWG through 4/0 AWG with the strand construction listed for each size. It applies the two-wire DC relationship using that resistance and does not estimate another temperature.

The limited AC mode uses the same product rows' AC resistance at 75°C and reactance at 60 Hz for a two-wire single-phase run. For conductor resistance R and reactance X in Ω/km, one-way length L in metres, current I, and lagging power-factor angle θ, the source-voltage relation is Vs² = VL² + 2VL·I·(Rloop cos θ + Xloop sin θ) + I²(Rloop² + Xloop²), where Rloop = 2RL/1000 and Xloop = 2XL/1000. The AC distance mode solves the same relation for a user-entered target. The result percentage is drop divided by supplied source voltage.

For the table-backed DC and AC modes, the result also shows one-conductor resistance for the entered length, the two-wire loop resistance, and resistive conductor loss I²Rloop using the entered current. AC loss uses the table's AC resistance; reactance is not counted as resistive loss. These values do not estimate conductor temperature or temperature rise. The manual effective-impedance mode cannot separate resistance from reactance, so it does not show the loss calculation.

This AC estimate assumes the product table's non-ferrous-conduit and one-diameter centre-to-centre spacing basis, a sinusoidal steady-state series model, and lagging power factor. It does not estimate another temperature, frequency or arrangement, and does not support three-phase, leading power factor, capacitance, harmonics, conductor selection or code acceptance. Manual AC mode continues to require user-supplied effective impedance.

The percentage is calculated as voltage drop divided by the supplied reference voltage. Results exclude unbalanced or harmonic-rich systems, split-phase neutral behaviour, conductor selection, breaker sizing, ampacity, protection and code compliance. Values remain in this page and are not saved.

Maximum distance is only the mathematical one-way length at which the chosen model reaches the user-entered target. It does not identify an acceptable target, account for starting conditions or select a conductor.

Worked example

For a two-wire single-phase circuit at 208 V, 50 A and 30.5 m one-way length, using an explicitly assumed effective impedance of 1.48 Ω/km, the formula gives 4.514 V, or approximately 2.170% of the reference voltage. These values illustrate the calculation; the impedance is not a default for any conductor.

For a reference voltage of 120 V and a user-entered 2.5% drop, direct conversion gives 3 V. This result does not identify an acceptable percentage for a circuit.

For a two-wire DC scenario at 48 V, 10 A and 20 m one-way length using the listed 10 AWG RW90 copper resistance of 3.41 Ω/km at 25°C, the estimate is 1.364 V drop (2.842%) and 13.640 W conductor loss. The two-wire loop resistance is 0.136 Ω. This example uses the table condition and does not estimate another conductor temperature.

For a two-wire single-phase AC case at 120 V, 10 A, 20 m and lagging power factor 0.8, using 12 AWG RW90 copper data, the exact source-voltage relation gives approximately 2.155 V drop and 1.795% of source voltage. One-conductor resistance is 0.131 Ω, two-wire loop resistance is 0.263 Ω, and resistive conductor loss is 26.280 W. This uses the table's 75°C resistance, 60 Hz reactance and stated reactance layout.

Only the display is rounded, to three decimal places; small nonzero results use scientific notation. No minimum or maximum acceptable percentage is applied.

Common questions

Is the length one way or out and back?

Enter one-way length in metres. Do not double it for single-phase; the formula already includes a factor of two.

Can I use this to choose a conductor size?

No. You can check a conductor you already specify in the limited RW90 table modes, or enter effective impedance in manual mode. The calculator does not compare candidates or recommend a conductor; ampacity, protection and applicable local requirements need their own assessment.

Does conductor loss predict wire temperature?

No. The I²R value estimates electrical power dissipated in the listed conductor resistance under the stated table condition. It does not predict conductor temperature, heat rise or an installation's thermal capacity.

Does a low percentage mean the installation passes?

No. This tool calculates a physical estimate and supplies no compliance or acceptability decision.

Report a problem or suggest a source. Calculation values are not automatically included.

Source

National Research Council Canada, User's Guide – National Energy Code of Canada for Buildings 2020, 2024 publication, Commentary on Part 7, Example 7-1, printed page 89 (PDF page 98). Source checked November 9, 2026.

Southwire CableTechSupport, RW90 Copper Circuit Sizes (14, 12 & 10 AWG), Canadian specification SPEC22061, table 2. The data mode uses its listed 25°C DC resistance column. AC resistance and reactance are not used by that mode.

Southwire CableTechSupport, SIMpull XHHW-2 / RW90 Copper specification PDF, SPEC10006 revision 1.000.142 (October 21, 2026), tables 1–2, and the current Canadian CableTechSupport detail page for SPEC10006. RW90 sizes 8 AWG through 4/0 AWG use the listed strand counts, 25°C DC resistance, 75°C AC resistance and 60 Hz reactance in this calculator's two-wire modes. The table and product page state the non-ferrous-conduit, one-diameter centre-to-centre reactance basis. Values in Ω/1000 ft are converted to Ω/km using 1,000 ft = 304.8 m. The downloadable spreadsheet export labels its AC resistance column 90°C; it is not used because the versioned PDF and current Canadian product page both specify 75°C. Ampacity columns are not used.

Southwire, RW90 Copper Circuit Sizes (14, 12 & 10 AWG), specification SPEC22061, states the inductive-impedance basis: non-ferrous conduit and one-diameter centre-to-centre spacing. Southwire, Power Cable Installation Guide, AC voltage-drop section, supplies the source-voltage phasor relationship. These are used only for the bounded AC estimate described above.

BCcampus, Basic Motor Control (2020), “Ohm's Law and Watt's Law.” The I²R relationship is used only to report conductor resistive loss; it does not provide a thermal model or conductor rating.

This tool is a physical calculation aid, not a Canadian Electrical Code determination. Verify inputs and the applicable requirements for the job.