Lighting layout calculator

Estimate a rectangular-room luminaire layout or convert area-average illuminance and light already reaching a surface. These modes do not predict point-by-point lighting.

Calculation inputs

Choose a lighting calculation

m

One straight room dimension; columns run along this direction.

m

The perpendicular room dimension; rows run along this direction.

lx

Supply a target appropriate to the work plane and task. No residential or code target is assumed.

lm

Total initial lamp/source lumens for one luminaire, on the same basis as its CU data. Do not mix lamp-based CU with already reduced luminaire output.

0–1

Use supported photometric data for the luminaire, room reflectances and mounting height above the work plane. This tool does not derive CU.

0–1

Use a documented combined maintenance/depreciation factor. Account for losses once; no generic percentage is supplied.

m

Supported maximum centre-to-centre spacing in this direction for the actual mounting height, orientation and photometry.

m

Supported maximum centre-to-centre spacing in the perpendicular direction. Do not infer it from a generic ceiling-height rule.

Enable JavaScript in your browser to use the calculator.

Lighting calculation result

Count and layout estimate

Enter the room, photometry and spacing values, then calculate.

Identical luminaires, an unobstructed rectangular room and compatible CU/source-lumen data are assumed. A complete grid can contain more luminaires than the lumen-only minimum. This is a proposed grid, not an optimized or approved lighting design.

Average illuminance does not establish minimum illuminance, uniformity, glare, beam coverage or code compliance. Check product photometry and the actual room before installation.

Inputs and interpretation

Obtain initial source lumens, coefficient of utilization (CU), light loss factor (LLF) and directional spacing limits for the chosen luminaire and room. CU depends on the room and mounting above the work plane; this calculator does not choose it from a fixture name or ceiling height.

The model supports positive CU and LLF no greater than 1. Use initial source lumens on the same basis as CU. Entering already maintained lumens and applying LLF again would count depreciation twice.

Inputs and results stay in this page and are not saved or transmitted.

Method and examples

Room area A = length × width in m². Lumen-only quantity N = ceil(target lx × A ÷ (initial source lm per luminaire × CU × LLF)). For the resulting grid, estimated maintained average E = grid quantity × source lm × CU × LLF ÷ A.

In the surface conversion mode, average illuminance E = incident luminous flux Φ ÷ surface area A, and incident flux Φ = E × A. The input flux must already reach the defined surface; source lumens are not treated as delivered light.

Begin with enough columns and rows to stay within each supplied spacing limit. If that grid has fewer than N luminaires, increase columns toward a proportionate room grid, limited by the rows already required, then add enough rows to reach N. This deterministic proposal does not search every arrangement for a minimum fixture count.

Centre spacing is room dimension divided by its column or row count. Each edge offset is half that spacing. Position column i at (i − ½) × length spacing and row j at (j − ½) × width spacing, counting from 1. The opposite-wall offset is the same.

Worked example

For an illustrative 6 m × 4 m room, target 200 lx, 1000 initial source lm per luminaire, CU 0.6 and LLF 0.8, the lumen-only minimum is 10 luminaires. With 2 m maximum spacing in both directions, the proposed complete grid is 4 columns × 3 rows, or 12 luminaires, with an estimated 240 lx average.

Length spacing is 1.5 m and width spacing is about 1.333 m; wall offsets are 0.75 m and about 0.667 m. Reducing both spacing limits to 1 m gives a 6 × 4 grid. These example inputs are not residential illuminance recommendations or product specifications.

Limits and interpretation

This is an average-lumen model and a cell-centre geometry convention. It does not calculate point illuminance, shadows, reflectance/CU, glare, daylight, beam overlap, obstructions, sloped ceilings or asymmetric room shapes. A regular grid and a stated spacing limit do not prove adequate light at every point.

Obtain a luminaire-specific photometric layout when those conditions matter. Recessed-luminaire clearances, insulation compatibility, electrical circuit loading, emergency lighting and applicable installation requirements are outside this model. The preview draws up to 400 positions; larger valid grids retain full numerical results.

Common questions

Why can the grid quantity exceed the lumen-only number?

Both directional spacing limits and complete rows/columns constrain the proposal. The lumen-only number is a lower bound for its average-light arithmetic, not a full placement plan.

Can I leave CU or LLF blank and use 1?

Only enter 1 when supported for the calculation basis. The tool requires both fields because assuming no utilization or maintenance losses can overstate the expected average.

Does the preview show the light pattern?

No. The points show proposed luminaire centres. They are not beam outlines, illuminance contours or a uniformity assessment.

Sources and model scope

National Research Council Canada, G. R. Newsham and D. M. Sander, The effect of office design on workstation lighting: a simulation study, NRCC-45357, section 4.4, printed page 12 / PDF page 14, uses the Lumen Method with source lumens, CU, depreciation and area. Only that general relationship is used here; its office geometry, targets and partition corrections are not imported. The equal-cell grid is this tool's stated layout convention.

Canadian Conservation Institute, Light, ultraviolet and infrared, glossary: lux is lumen per square metre. No museum illumination target is used. Sources checked November 10, 2026.

Report a problem or suggest a source; inputs are not attached automatically.